The IP Code uses a mandatory two-numeral system, IPXX, optionally extended by supplementary letters to indicate specific protection levels and test conditions

The degree of protection provided by an enclosure is designated by the IP Code in a specific arrangement consisting of up to five parts:

  1. Code Letters (IP): Indicating “International Protection”.
  2. First Characteristic Numeral (0 to 6, or X): Indicating protection against access to hazardous parts and solid foreign objects.
  3. Second Characteristic Numeral (0 to 9, or X): Indicating protection against ingress of water with harmful effects.
  4. Additional Letter (Optional: A, B, C, D): Indicating a degree of protection against access to hazardous parts that is higher than that shown by the first characteristic numeral.
  5. Supplementary Letter (Optional: H, M, S, W): Providing supplementary information specific to high voltage, motion during water testing, stationary testing, or weather conditions.

If a characteristic numeral is not required to be specified, it must be replaced by the letter “X” (“XX” if both are omitted). For example, IPX5 means the protection against solids is omitted from specification, but it is protected against water jets. Conversely, optional letters can simply be omitted without replacement, such as in IP44.

If multiple degrees of protection against water are provided, they can be listed sequentially, such as IPX5/IPX7/IPX9, indicating suitability for water jets, temporary immersion, and high pressure/temperature jets. If more than one supplementary letter is used (e.g., M and S are mutually exclusive, but H and W could be combined), they must be placed in alphabetical sequence. This structured arrangement allows the IP Code to convey complex information about mechanical and fluid resilience, as well as the specific conditions under which the product was tested.

Related Articles

The first characteristic numeral (1-4) simultaneously classifies protection against human access using specific probes and against the physical ingress of similarly sized solid objects

The first characteristic numeral (1 through 4) always implies the satisfaction of two conditions simultaneously: protection of persons against access to hazardous parts, and protection of the equipment against the ingress of solid foreign objects. This dual role ensures both operational safety and physical integrity against external contamination. The definitions for protection against access rely…

The IEC 60529 standard establishes a unified classification system for enclosure protection against three primary hazards, applicable up to 72.5 kV

The standard IEC 60529 describes a system for classifying the degrees of protection provided by enclosures for electrical equipment. This system is generally suitable for most electrical equipment, provided the rated voltage does not exceed 72.5 kV. The fundamental objective of this standard is multi-faceted: to provide definitions for degrees of protection, establish designations for…

IEC60529 Brief Introduction to IP Code

The IP Code is a coding system designed to indicate the degrees of protection provided by enclosures against access to hazardous parts, ingress of solid foreign objects, and ingress of water . It consists of the letters “IP” followed by two characteristic numerals, with optional additional and supplementary letters . The first numeral (0-6) indicates protection…

First Characteristic Numeral 5 and 6: Detailed Dust Management and Testing

IP5X mandates limited, harmless dust ingress while IP6X requires absolute dust-tightness, both verified using standardized vacuum and duration tests. The highest two degrees of the first characteristic numeral specifically address the penetration of dust. These levels require specialized testing using a dust chamber (Figure 2) and finely sifted talcum powder. The testing procedure depends on…

IP ratings General Testing Requirements, Acceptance Criteria, and Compliance Responsibility

Verification of IP ratings relies on standardized atmospheric conditions, non-harmful ingress acceptance criteria, and the final manufacturer’s responsibility for the completed product. All tests specified in IEC 60529 are type tests. To ensure repeatability, they should be carried out under standard atmospheric conditions, unless otherwise specified, including a temperature range of 15 °C to 35…